PROJECT: HVJF-S Partial Discharge Detector

HVJF-S Partial Discharge Detector

Other names: Partial Discharge Tester/ Analyzer

                    PD Tester

Operation guide Of HDJF-S  Ultrasonic Partial Discharge Detector:

Pls Click here.

Applicable scope:

  The non-intrusive mode is adopted to detect and locate the partial discharge defects of the high-voltage electric equipment.

Sensor configuration

    -Standard: UA, TEV

    -Optional: Sensor network for transformer, high frequency sensor for GIS, sensor for high-voltage cable,or other senors customized according to user's requirements.

Detection principle:

  UHF (Ultra High Frequency) method, UA (Ultrasonic Analysis) method and TEV (Transient Earth Voltage) method.

Detection frequency band:

  UA: 40~200KHz

  TEV: 3~100MHz

  UHF: 300~2000MHz.

Measurement range:

  UA: -90~80dB

  TEV: -80~10dBm

  UHF: -80~10dBm.

Sensitivity: the minimum sensitivity is 10pC (specifically determined by the distance between the sensor and the discharge source).

Sensor:

  a) Ultrasonic sensor: 20~200(kHz);

  b) EV (Transient Earth Voltage) sensor: 5 ~ 100MHz;

  c) UHF sensor: 300~2000(MHz), with directional reception characteristic.

Software function:

  a) Continuously detect UHF, TEV and ultrasonic signals to judge whether there is any partial discharge;

  b) Display the variation tendency of the detected signal in a real-time manner to intuitionally judge the development of the partial discharge signal;

  c) Field data storage function;

Description:

Partial discharge does not cause the electric discharge of a completely short-circuited electrode. Such discharge usually has a very small amplitude value, but it will certainly cause the continuous deterioration of the property of the insulation layer and finally cause electric equipment fault.

The partial discharge emits energy in following manners:

Electromagnetic energy: radio wave, light and heat;

Sound energy: sound wave and ultrasonic wave;

Gas: ozone and nitric oxide.

The most practical non-intrusive detection technologies are all based on the detection of the high-frequency signals and the ultrasonic signals in the electromagnetic spectrum. The product is an instrument which has simple operation and is specially developed for detecting the activities of electromagnetic waves and ultrasonic waves.

Operation Videos of HVJF-S Partial Discharge Detector PURCHASED, pls click to check.

james1

Share

Recent Posts

Tech: X Ray Machine Safety Cautions

    Tech: X Ray Machine Safety Cautions     Security prompt High voltage danger, watch out for electricity Ionizing…

2025-04-06

Video of HVPD-IR-SW 3 In 1 Sound Wave Tester, Partial Discharge Tester, Infrared Tester

              Video of HVPD-IR-SW 3 In 1 Sound Wave Tester, Partial Discharge Tester, Infrared Tester…

2025-03-29

Tech: Why can't the DC system be grounded?

Tech: Why can't the DC system be grounded?   I. Why can't the DC system be grounded? The DC system…

2025-03-22

Operation Video: HVGC-982 300V 250A Battery Pack Discharge Tester

                Operation Video: HVGC-982 300V 250A Battery Pack Discharge Tester Over View Tested object:…

2025-03-11

Video: Do hipot test to VT Voltage Transformer with HVTF-1600kVA/600kV VF Resonance Hi-pot Test Device

        Video: Do hipot test to VT Voltage Transformer with HVTF-1600kVA/600kV VF Resonance Hi-pot Test Device…

2025-02-28

Operation Video of HVVLF-YT-80KV Integrated VLF Hipot Test Set

Operation Video of HVVLF-YT-80KV Integrated VLF Hipot Test Set Operation Video of HVVLF-YT-80KV Integrated VLF Hipot Test Set, Please kindly check.…

2025-02-19

Our website uses cookies to improve our website and improve the user experience.